VAV with terminal reheat vs standard VAV
One-line orientation
VAV with terminal reheat adds a heating coil at each VAV box to allow per-zone temperature precision — the exam tests knowing this wastes energy and when that tradeoff is justified.
Key points
-
Standard VAV recap: varies the volume of centrally cooled air sent to each zone; each zone thermostat modulates a damper. Efficient for variable cooling loads; no local heating capability at the terminal.
-
VAV with terminal reheat: adds a heating coil (electric resistance or hot-water) inside each VAV box. The central AHU still supplies cool air; the reheat coil raises the air temperature locally before it enters the zone.
-
Operation: the system supplies cool air to every zone simultaneously. Zones that need cooling receive it by increasing airflow; zones that need heating (or need less cooling) receive reheated air from the local coil.
-
Energy penalty: the system cools air centrally and then reheats it locally — both processes consume energy. This simultaneous heating-and-cooling loop is an inherent inefficiency and is the reason the system is flagged in energy codes.
-
When justified: choose VAV reheat when zones need minimum ventilation airflow and local heating. This is common in hospitals, laboratories, clean rooms, and other spaces that need tight local control.
Confusions / comparison
| Standard VAV | VAV with terminal reheat | |
|---|---|---|
| Terminal unit | Damper only | Damper + heating coil |
| Zone temperature control | Cooling only (throttle airflow) | Cooling and heating per zone |
| Energy efficiency | High | Lower — simultaneous heat/cool |
| First cost | Lower | Higher (coils + controls) |
| Best application | Variable-load office/commercial | Hospitals, labs, precision spaces |
Related
→ HVAC: single vs multi-zone (VAV reheat is a multi-zone sub-type) · dual-duct system (another energy-intensive precision-control approach) · HVAC distribution systems (all-air context for VAV family).
Spotted an issue with this card? Tell us →