Sheet LS-106
Accessibilityconcept
Accessible reach ranges, protrusions, and floor transitions
One-line orientation
Accessibility rules separately limit how high a person must reach, how far an object may project into a path, and how a floor level may change. Their numbers are easy to confuse.
Key points
- Reach range (general): accessible controls, switches, and outlets must fall between 15 inches and 48 inches AFF — the zone a seated wheelchair user can reach without overexertion.
- Side reach is NOT higher: the 2010 ADA Standards cap the unobstructed side reach at the same 48 inches (§308.3.1) — the 54-inch side-reach maximum comes from the superseded 1991 ADAAG. Reaching over an obstruction can lower the allowed height (48” over an obstruction up to 10” deep; 46” over one 10–24” deep).
- Protrusion limit: objects may project no more than 4 inches into a circulation path. If the protrusion exceeds 4 inches, a barrier (railing, curb, low wall) or recessing is required to signal its presence.
- Protrusion hazard zone: the dangerous band is 27 to 80 inches AFF. Below 27 inches a cane can detect the object; above 80 inches the object clears head height. Between those values the obstruction is invisible to cane users — the source of the rule.
- Floor transitions — vertical: a change in floor level up to 1/4 inch may be vertical (no bevel needed).
- Floor transitions — beveled: between 1/4 inch and 1/2 inch total height, a bevel at a maximum slope of 1:2 is required. A change exceeding 1/2 inch is no longer a transition — it becomes a ramp.
Confusions / comparison
| Rule | Lower limit | Upper limit | Note |
|---|---|---|---|
| Reach range | 15” AFF | 48” AFF (forward and side) | Controls, outlets, thermostats |
| Protrusion hazard zone | 27” AFF | 80” AFF | Objects here must be ≤ 4” deep or mitigated |
| Floor transition — vertical | 0 | ≤ 1/4” | No bevel required |
| Floor transition — beveled | > 1/4” | ≤ 1/2” | Bevel ≤ 1:2 required |
| Transition too tall | > 1/2” | — | Must be treated as a ramp |
| Protrusion detail | Limit |
|---|---|
| Max depth into path | 4 inches |
| Hazard zone (height) | 27”–80” AFF |
| Mitigation if > 4” | Barrier, curb, recessing, or ground-level indicator |