Hydronic terminals: fan-coil units, chilled beams, and radiant systems compared
One-line orientation
Hydronic terminals deliver heating and cooling locally via water-carrying pipes rather than large duct runs — the exam tests which terminal type suits a given constraint (noise, humidity, floor-to-floor height, or dew-point risk).
Key points
- Fan-Coil Unit (FCU): a water coil plus a fan; circulates room air over the coil for local
heating or cooling. No central ductwork needed. Common in hotels, apartments, and office
perimeter zones.
- Fan-coil systems generally use a separate source of ventilation air. Some systems bring outdoor air locally. A fan-coil can remove some moisture when its coil is below the dew point, but it does not closely control humidity.
- Noise: the local fan is audible, so an FCU is generally noisier than a fanless chilled beam or radiant system.
- Active Chilled Beam (ACB): a ceiling-mounted unit fed by (a) chilled water and (b) a primary
air supply. Primary air is induced through nozzles, drawing room air across the coil — achieves
both ventilation and sensible cooling in one device.
- High cooling efficiency; lower noise than FCU; integrates into shallow ceiling plenum.
- Limitation: not suited to high-latent / high-humidity spaces because the beam handles sensible cooling only; dehumidification must come from the primary air side.
- Radiant Cooling (and Heating): chilled (or warm) water circulates through tubes embedded in
the floor, ceiling, or panels. Heat exchange is by radiation and natural convection — no fans,
completely silent.
- Critical constraint: surface temperature must remain above the room dew point at all times; if the surface is colder than the dew-point temperature, condensation forms on the floor or ceiling.
- Best in low-latent environments (dry climates or spaces with tight humidity control).
- Closed-Loop Heat Pump (water-source): a loop of condenser water circulates at a moderate temperature; individual heat pumps in each zone either reject heat to or extract heat from the loop. Allows simultaneous heating in one zone and cooling in another.
Confusions / comparison
| Terminal | Medium | Fan? | Ventilation | Humidity control | Noise | Key constraint |
|---|---|---|---|---|---|---|
| Fan-coil unit (FCU) | water | yes | separate or local outdoor-air source | limited; coil can dehumidify | moderate | fan noise; ventilation source required |
| Active chilled beam | water + primary air | no (induced) | built-in via primary air | limited (sensible beam) | low | no high-latent-load spaces |
| Radiant cooling | water | no | separate system needed | none | silent | surface ≥ dew point |
| Closed-loop heat pump | water loop | yes | needs DOAS | moderate | moderate | loop temp management |
Related
→ HVAC distribution systems (all-water family) · HVAC system selection (noise / space criteria) · Plumbing: hydronic piping configurations (1-pipe / 2-pipe / 4-pipe).
Spotted an issue with this card? Tell us →