← Project Planning & Design

Sheet S-114
PPDPDD CE

Steelconcept

Steel connections: shear vs moment, bolted vs welded, slip-critical vs bearing

One-line orientation

How steel members are joined — by force transferred (shear vs moment) and by method (bolted vs welded, slip-critical vs bearing) — is heavily tested because it controls how the frame behaves under gravity, wind, and seismic loads.

Key points

  • By force transferred:
    • Shear / simple connection: joins the web only (clip or seat angles). Carries gravity/shear, allows rotation at the beam end (acts pinned), does not resist bending.
    • Moment connection: joins the flanges as well, making the joint rigid. Transfers both shear and bending moment; comes as fully restrained or partially restrained.
  • By method — bolted vs welded:
    • Bolted: fast field erection, less skilled labor; uses high-strength bolts (ASTM F3125 Grades A325 and A490). The older A325/A490 names are still the familiar grade names.
    • Welded: continuous and stiff; a sound weld can be stronger than the base metal, and suits complex geometry — but needs skilled labor, inspection/QC, and control of thermal distortion.
  • Bolted connection behavior — slip-critical vs bearing:
    • Use a slip-critical connection when slip would harm performance. Seismic loading alone does not make every bolted joint slip-critical.
    • Bearing (bearing/shear): minor slip allowed; resistance develops when the bolt shank bears on the hole. Simpler and cheaper where slight movement is acceptable.
  • Bolted detailing:
    • Standard holes — slightly larger than the bolt for fit-up, often about +1/16 in for common sizes; use AISC/RCSC tables for exact dimensions.
    • Slotted holes — allow movement or tolerance.
    • Washers — distribute load and help maintain preload.

Confusions / comparison

Shear / simpleMoment
ConnectedWeb only (angles)Web and flanges
TransfersGravity/shearShear + bending
End behavesPinned — rotatesRigid — restrained
ExampleSeated/clip-angle connectionWelded-flange (FR/PR) connection
Slip-criticalBearing
Resists viaFriction (pretension/clamping)Bolt shank bearing on hole
SlipNoneMinor slip allowed
Use whenFatigue, seismic, reversal, slotted holesSlip acceptable; simpler/cheaper

→ Steel shapes and members (this module): the members being joined · Steel lateral systems (this module): moment connections build moment frames; bolted braces build braced frames · Steel types and production (this module): why weldable low-carbon steel matters.