HVAC distribution systems: all-air / all-water / air-water selection
One-line orientation
HVAC systems are categorized by the medium that carries heating/cooling to the space — the exam tests which type to choose under given constraints and each type’s control logic.
Key points
- All-air: single-zone, CAV, VAV, dual-duct, reheat. Ducted, centrally treated air is delivered to the space; the duct itself is the thermal medium, so it needs the most vertical shaft and ceiling space.
- All-water (hydronic): fan-coil units, water-source heat pumps. Water carries the thermal energy and air is conditioned locally at the terminal; pipes are small, so it saves duct space but needs local ventilation handling.
- Air-water: induction units, etc.; a small central primary air supply (for ventilation) plus a local water coil at the terminal (for load) — balances the two.
- VAV vs CAV: VAV varies air volume at a constant supply temperature (efficient, good for variable loads); CAV holds constant volume and varies the supply temperature (simpler, less efficient).
Confusions / comparison
| Medium | Terminal handling | Typical use | What it saves | |
|---|---|---|---|---|
| All-air | air | central | large spaces, high ventilation | central control, easy maintenance |
| All-water | water | local | tight floor-to-floor, perimeter loads | vertical duct space |
| Air-water | both | local + some air | high-rise perimeter zones | balances ventilation and space |
All-air control logic — VAV vs CAV (the most-tested air-side distinction, otherwise only in the drills):
| Criterion | VAV (variable air volume) | CAV (constant air volume) |
|---|---|---|
| What varies | Air volume, at a constant supply temperature | Supply temperature, at a constant volume |
| Efficiency | Higher — throttles airflow to match the load | Lower — moves full airflow regardless of load |
| Best fit | Variable or multi-zone loads | Simple, steady single-zone loads |
HVAC distribution: the carrying medium sets how much building it eats
SCHEMATICNamed by what carries the heat — air, water, or both — and where it is conditioned. Air needs the deepest shaft and ceiling plenum; water the least.
View diagram Hide diagram
Scroll horizontally to explore
- air — duct / primary air
- water — supply / return pipe pair
- induction — air nozzle + water coil, no fan
- fan-coil — fan + water coil
The duct is itself the thermal medium, so all-air's shaft and ceiling plenum run deepest — they eat the most of a fixed floor-to-floor. A tight floor-to-floor selects water-based distribution (all-water or air-water), which needs far less vertical space.