← Construction & Evaluation

Sheet E-110
PPDPDD PACE

Lightingconcept

Lamp types: incandescent, halogen, fluorescent, HID, and LED compared

One-line orientation

Lamp selection trades off four variables — CRI, CCT, efficacy, and lifespan — and the exam tests which lamp type fits which application, which require ballasts, and which pose mercury disposal requirements.

Key points

Five lamp families:

  • Incandescent: a tungsten filament produces light by heating to incandescence. It dims easily but creates high heat. It is largely replaced by LED, though it remains useful where instant warm dimming is important.
  • Halogen: an incandescent lamp with halogen gas. It runs hotter than standard incandescent and has largely been replaced by LED.
  • Fluorescent: an electric discharge creates ultraviolet light, which a phosphor coating converts to visible light. It requires a ballast, contains mercury, and requires regulated disposal.
  • HID — Metal Halide: electric arc through metal halide gas. CRI ~85, CCT ~4000 K (neutral white), efficacy 80–100 lm/W, life 10,000–20,000 hrs. Requires ballast. Contains mercury. Long warm-up time (minutes) before full output. Applications: stadiums, gymnasiums, industrial.
  • HID — High-Pressure Sodium (HPS): sodium-gas discharge with a long warm-up time and very poor CRI. It suits street and exterior security lighting where color accuracy is unimportant.
  • LED: a semiconductor junction converts electricity directly to light. It needs a compatible dimmer and driver heat management. Main trade-offs are higher initial cost and gradual lumen depreciation (L70).

Confusions / comparison

LampCRICCTEfficacy (lm/W)Life (hrs)Ballast?Mercury?
Incandescent~100~2500 K~20~2,000NoNo
Halogen~100~2700–3000 K15–25 (std); 25–35 (IRC)~4,000NoNo
Fluorescent75–853000–6500 K60–9010,000–15,000YesYes
Metal Halide (HID)~85~4000 K80–10010,000–20,000YesYes
High-Pres. Sodium (HID)~20~2000 K~10015,000–25,000YesYes (regulated disposal required)
LED85+2700–6500+ K90–12050,000–100,000NoNo
ApplicationBest lampReason
Residential / hospitality ambianceIncandescent or warm LEDCRI ~100, CCT ~2700 K, easy dimming
Office / general commercialLED or fluorescentEfficacy, long life, range of CCT
Retail / art galleryHigh-CRI LED (CRI 90+)Color accuracy for merchandise / artwork
Stadiums / sports facilitiesMetal Halide HID or LEDHigh output, good CRI, large area
Street / parking / securityHPS (legacy) or LED (preferred now)High efficacy, long life; LED now dominant

Lamp types reduce to four performance patterns

QUALITATIVE MEMORY MAP

Read the same three meters in every panel: efficacy, color rendering, and life

View diagram Hide diagram

Scroll horizontally to explore

Four repeatable lamp-performance patterns Four matched panels compare lamp families with the same three qualitative meters, each headed by a line drawing of that family's lamp. Incandescent and halogen, drawn as an A-shaped bulb with a filament and screw base, show low efficacy, very high color rendering, and short life. Fluorescent and metal halide, drawn as a pinned linear tube, show middle-range performance and are marked mercury and ballast. High-pressure sodium, drawn as an outer envelope with a slim arc tube inside it, shows high efficacy, very poor color rendering, and long life and is also marked mercury and ballast. LED, drawn as a die on a finned board, is the only blue panel and shows high efficacy, high color rendering, and the longest life. Incandescent + halogencolor leaders · heat-heavyno HgEfficacylowCRIvery highLifeshort Fluorescent + metal halidebalanced middle groundHg · ballastEfficacymiddleCRIgoodLifemedium High-pressure sodiumefficiency without colorHg · ballastEfficacyhighCRIvery poorLifelong LEDthe all-around winnerno HgEfficacyhighCRIhighLifelongest

HPS is the trap: high efficacy and long life do not compensate for very poor color rendering (CRI about 20).

Qualitative grouping for recall; use the card table for exact ranges. Hg families also require a ballast. HID lamps also need time: roughly 1–4 minutes to strike from cold and 2–8 minutes to re-strike once hot, so they suit spaces that stay lit.

→ Lighting: Lighting metrics (CRI/CCT/efficacy definitions) · Illuminance & daylight (how lamp choice affects fc calculation via lumens per lamp) · Lighting controls (dimming compatibility: incandescent/halogen = easy; fluorescent = special ballast; LED = compatible dimmer required).